    AI control cuts cooling energy in Google's data centers

    Google and DeepMind trained neural networks on years of sensor data, first to advise data center operators on cooling settings and then to run the cooling plants themselves under operator supervision.

    GoogleUnited StatesCloud and data centersIn production since 2018
    Scale
    Multiple Google data centers
    Scenario
    Data center cooling optimization
    Business function
    Energy and asset operations
    Who built it
    Built with a partner (Google DeepMind)
    Human oversight
    Acts under watch
    Organization
    Enterprise, part of Alphabet
    AI types
    Machine learning, Optimization
    Sites
    multiple Google data centres

    Sources and their publishers

    This case study draws on reporting by the following publishers. Enterprise AI Case Studies combined these accounts and added its own explanation. The reporting, and every passage quoted from it, belongs to whoever published or supplied it.

    1. Google DeepMind

    2. MIT Technology Review

    3. Google

    4. arXiv

    5. Meta

    6. etalytics

    7. Data Center Knowledge

    tl;drBy August 2018, AI control had improved cooling efficiency in Google data centers by around 30%.See the results

    View the solutionBuild this solution yourself

    In August 2018, Google and DeepMind said that an AI system controlled the cooling of several Google data centers while the operators supervised2, 3. The AI chose the plant’s settings every five minutes, and the site’s own control system checked them before they reached the equipment2.

    The system grew out of a recommendation engine whose advice operators applied by hand2. In a test on a live data center, reported in July 2016, that engine cut the energy used for cooling by 40%1.

    Under direct control, cooling efficiency in kW/ton was 12% better than the historical baseline at launch and around 30% better nine months later2.

    Before the deployment

    Google’s data centers were already highly optimized when this work began, which made further gains hard to find1, 4. The cooling plants had the following problems:

    • Slowing gains: Annualized fleet-wide power usage effectiveness (PUE), the ratio of total facility energy to IT energy, fell from 1.21 in 2008 to 1.12 in 2013. The pace slowed because returns diminished and existing cooling technology reached its limits1, 4.
    • Standard practices in place: Hot air containment and water side economization were already commonplace in large data centers4.
    • Nonlinear equipment: Pumps, chillers and cooling towers remove the heat from the servers behind Google Search, Gmail and YouTube. The equipment, its operation and the environment interact in nonlinear ways that formula-based engineering and human intuition often miss1.
    • Rules that couldn’t adapt: Nobody can write rules and heuristics for every operating scenario, so the control logic couldn’t adapt quickly to changes such as the weather1.
    • Changes that couldn’t be predicted: A change to the cold aisle setpoint shifts the load across chillers, cooling towers, heat exchangers and pumps, so standard formulas produce large errors. An operator couldn’t predict what a configuration change would do to PUE before making it. Engineers couldn’t try every combination either, because the IT load and the weather kept moving and the data center had to stay stable4.

    The plants did have data. A typical large data center generates millions of data points a day across thousands of sensors, and the data was rarely used for anything but monitoring4.

    What was built

    The system predicts how candidate cooling actions will change energy use, and it applies the actions that use the least energy within the operators’ limits2. The work is divided as follows:

    • Neural network ensembles: Predict how combinations of potential actions, of which there are billions, will change future energy use2.
    • Cloud-based AI: Estimates its confidence in each action and drops the actions with low confidence. It then picks the lowest-energy actions that satisfy an internal list of safety constraints, which the operators define2.
    • Local control system: Verifies each instruction against its own set of constraints before it implements it. This redundant check keeps the plant within local limits and leaves the operators in charge of the operating boundaries2.
    • Data center operators: Can exit AI control mode at any time. The plant then runs on the on-site rules and heuristics of standard industrial automation2. A manager can watch the system, see its confidence in each change, and step in3.
    • Data center staff: Still did all the maintenance in 2018. Instead of tuning the plant themselves, they could spend more of their time on preventive maintenance and repairs10.

    The system uses eight safety mechanisms. Three of them are estimating uncertainty, two-layer verification, and the operators’ exit from AI control2.

    DeepMind confined the system’s optimization boundaries to a narrower operating regime to put safety and reliability first. It said that it would widen them as the technology matured2. Joe Kava, Google’s vice president of data centers, explained why such limits matter: “If you were to tell a machine to optimize for PUE, the machine might tell you to shut down all of the servers”10.

    From advice to control

    Google moved from a model that advised people to an AI that acts on the plant, in the following stages:

    1. PUE model: Jim Gao, then a Google data center engineer, built a recommendation engine around a neural network that predicted PUE4, 10. It was trained on about two years of five-minute data with 19 input variables, such as IT load, weather and equipment setpoints4. Gao chose a neural network because it doesn’t need the interactions between features defined in advance4.
    2. Recommendations from DeepMind: DeepMind researchers trained an ensemble of deep neural networks on the sensor history, with average future PUE as the target1. Two more ensembles predicted temperature and pressure over the next hour, so that each recommended action could be checked against the operating constraints1. Operators still vetted and implemented every action2.
    3. Direct control: Operators said that the recommendations had taught them new practices, such as spreading the cooling load across more equipment. They also said that applying the advice took too much effort and supervision, and they wanted to know whether the same savings could come without the manual work2. The answer was a “tier-two” automated control system that makes the cooling-plant adjustments on its own, continuously10.

    “And you start to put in the guardrails to make sure that bad things can’t happen, and then you start to launch fully automated systems instead of semiautomated systems”

    Joe Kava, vice president of data centers at Google10

    Rollout

    In 2018, Kava described a site-by-site rollout, because each data center’s cooling is designed for its location and a model has to be trained for each site’s architecture10. In his account, more runtime and data make the algorithm better and the team more comfortable with giving it control10. Where the fully automated systems run better, Google deploys more of them10.

    Figure 1From a PUE model to direct AI control of cooling
    From a PUE model to direct AI control of coolingIn 2014 Google revealed it was using AI for data center efficiency, and Jim Gao's paper described a neural network model of PUE validated at Google data centers. In July 2016 DeepMind reported a test of an AI recommendation system on a live data center. On 2 August 2018 Joe Kava said Google was rolling out a tier-two automated control system. On 17 August 2018 DeepMind reported direct AI control of cooling in multiple Google data centers. In December 2022 DeepMind, Google and Trane researchers reported a similar algorithm controlling the chiller plants of two commercial buildings.20142014 · PUE neural network in use at Google sites · Documented in sources [4] [10]PUE neural network in use at Google sitesJul 2016Jul 2016 · Recommendation system tested on a live site · Documented in source [1]Recommendation systemtested on a live site2 Aug 20182 Aug 2018 · Tier-two automated control being rolled out · Documented in source [10]Tier-two automatedcontrol being rolled out17 Aug 201817 Aug 2018 · Direct AI control in multiple data centers · Documented in sources [2] [3]Direct AI control in multiple data centersDec 2022Dec 2022 · Similar algorithm tested with Trane · Documented in source [5]Similar algorithm tested with TraneFrom a PUE model to direct AI control of coolingIn 2014 Google revealed it was using AI for data center efficiency, and Jim Gao's paper described a neural network model of PUE validated at Google data centers. In July 2016 DeepMind reported a test of an AI recommendation system on a live data center. On 2 August 2018 Joe Kava said Google was rolling out a tier-two automated control system. On 17 August 2018 DeepMind reported direct AI control of cooling in multiple Google data centers. In December 2022 DeepMind, Google and Trane researchers reported a similar algorithm controlling the chiller plants of two commercial buildings.20142014 · PUE neural network in use at Google sites · Documented in sources [4] [10]PUE neural networkin use at Google sites3 yrsJul 2016Jul 2016 · Recommendation system tested on a live site · Documented in source [1]Recommendationsystem tested ona live site2 yrs 1 mo2 Aug 20182 Aug 2018 · Tier-two automated control being rolled out · Documented in source [10]Tier-two automatedcontrol being rolled out17 Aug 201817 Aug 2018 · Direct AI control in multiple data centers · Documented in sources [2] [3]Direct AI control inmultiple data centers4 yrs 4 moDec 2022Dec 2022 · Similar algorithm tested with Trane · Documented in source [5]Similar algorithmtested with Trane
    • Key milestone
    Sources [1][2][3][4][5][10]
    Google validated a model and tested recommendations on a live site before it let the AI act on the plant itself.

    Technology and architecture

    Figure 2Where the AI sits in Google's cooling control loop
    Where the AI sits in Google's cooling control loopThousands of sensors in a Google data center send a snapshot of the cooling plant to neural network ensembles in a cloud-based AI system every five minutes. Data gathered from Google data centers trains the ensembles, one model per site. Their predictions go to an action selection step, which drops low-confidence actions and applies safety constraints defined by the data center operators. Chosen actions go to the local control system at the site, which verifies them and sets the pumps, chillers and cooling towers. Operators can take the plant out of AI control through the local control system. Logging new sensor readings into the training history is inferred.snapshot every 5 minutes (data) · Documented in source [2]logged readings (data) · Inferred, not documented in the sources (builds on sources [1] [2])training data (data) · Documented in sources [3] [10]predicted energy (data) · Documented in source [2]define (trigger or control) · Documented in source [2]limits (trigger or control) · Documented in source [2]chosen actions (trigger or control) · Documented in source [2]exit AI mode (trigger or control) · Documented in source [2]verified setpoints (trigger or control) · Documented in source [2]CLOUD-BASED AI SYSTEMDATA CENTER CONTROLSThousands of sensors · Device · Documented in sources [1] [2]DEVICEThousandsof sensorsHistorical sensor data · Data · Documented in source [3]DATAHistoricalsensor dataNeural network ensembles · AI model · Documented in sources [1] [2]AI MODELNeuralnetworkensemblesOperator safety constraints · Data · Documented in source [2]DATAOperatorsafetyconstraintsAction selection · Step · Documented in source [2]ActionselectionData center operators · Team · Documented in sources [2] [3]TEAMData centeroperatorsLocal control system · System · Documented in source [2]SYSTEMLocal controlsystemPumps, chillers, cooling towers · Device · Documented in source [1]DEVICEPumps,chillers,cooling towerssnapshot every5 minutesloggedreadingstraining datapredictedenergydefinelimitschosen actionsexit AI modeverifiedsetpointsWhere the AI sits in Google's cooling control loopThousands of sensors in a Google data center send a snapshot of the cooling plant to neural network ensembles in a cloud-based AI system every five minutes. Data gathered from Google data centers trains the ensembles, one model per site. Their predictions go to an action selection step, which drops low-confidence actions and applies safety constraints defined by the data center operators. Chosen actions go to the local control system at the site, which verifies them and sets the pumps, chillers and cooling towers. Operators can take the plant out of AI control through the local control system. Logging new sensor readings into the training history is inferred.snapshot every 5 minutes (data) · Documented in source [2]logged readings (data) · Inferred, not documented in the sources (builds on sources [1] [2])training data (data) · Documented in sources [3] [10]predicted energy (data) · Documented in source [2]define (trigger or control) · Documented in source [2]limits (trigger or control) · Documented in source [2]chosen actions (trigger or control) · Documented in source [2]exit AI mode (trigger or control) · Documented in source [2]verified setpoints (trigger or control) · Documented in source [2]CLOUD-BASED AI SYSTEMDATA CENTER CONTROLSThousands of sensors · Device · Documented in sources [1] [2]DEVICEThousands of sensorsHistorical sensor data · Data · Documented in source [3]DATAHistorical sensor dataNeural network ensembles · AI model · Documented in sources [1] [2]AI MODELNeural networkensemblesOperator safety constraints · Data · Documented in source [2]DATAOperator safetyconstraintsAction selection · Step · Documented in source [2]Action selectionData center operators · Team · Documented in sources [2] [3]TEAMData center operatorsLocal control system · System · Documented in source [2]SYSTEMLocal control systemPumps, chillers, cooling towers · Device · Documented in source [1]DEVICEPumps, chillers,cooling towerssnapshot every 5 minuteslogged readingstraining datapredicted energydefinelimitschosen actionsexit AI modeverified setpoints
    • AI component
    • Data
    • Trigger or control
    • Inferred, not documented
    Sources [1][2][3][10]
    The cloud AI chooses cooling actions, and operator constraints and the local control system both check them before the plant moves.

    The cloud system decides, and the site’s own control system has the last word on what reaches the equipment1, 2. The following table lists the parts of the solution.

    Layer What they used Role Source
    Predictive model Ensemble of deep neural networks Predicts how combinations of candidate actions change future energy use 1, 2
    Control and autonomy model Cloud-based AI control system Pulls a snapshot every five minutes, drops low-confidence actions, picks the lowest-energy safe actions 2
    Guardrails Operator-defined safety constraints The list every action is vetted against before it leaves the cloud 2
    Control system Local control system Verifies each instruction against its own constraints, implements it, runs the fallback rules 2
    Sensors and telemetry Thousands of sensors Supply the five-minute snapshot and the training history 1, 2
    Machines, robots and vehicles Pumps, chillers and cooling towers The cooling plant whose setpoints the system adjusts 1, 10

    Data inputs

    The system uses the following data:

    • Plant snapshot: Every five minutes, the cloud AI pulls a snapshot of the cooling system from thousands of sensors2.
    • Weather and load variables: The controller reads 21 variables, among them outside air temperature, barometric pressure, wet-bulb and dry-bulb temperature, dew point, the power load, and the air pressure behind the servers. Based on the weather and the load, it optimizes PUE10.
    • Training history: Sensor data gathered from Google data centers, such as temperatures, power, pump speeds and setpoints, trains the models1, 3.

    The system gets better over time with more data2. It’s probably retrained on the logged results of its own operation.

    Control algorithm

    A 2022 paper by DeepMind, Google and Trane researchers describes a core algorithm that it calls similar to the one used to cool Google’s data centers5. At each time step, the algorithm works as follows:

    1. An ensemble of neural networks predicts the energy consumption of each action and whether the action would violate each constraint5.
    2. The algorithm discards the actions that are known or predicted to violate a constraint5.
    3. It picks one of the remaining actions with an exploration trade-off based on the ensemble’s standard deviation5.

    MIT Technology Review describes the approach as reinforcement learning (RL), which learns through trial and error3. At NeurIPS in 2018, Google researchers also described an RL agent that regulates temperatures and airflow on a server floor6.

    One five-minute control cycle

    Each cycle runs from the sensors through the cloud AI to the local control system, and every action passes two constraint checks2.

    Figure 3One five-minute cycle of AI cooling control
    One five-minute cycle of AI cooling controlThe plant sensors send a snapshot of the cooling system to the cloud AI. The cloud AI predicts the energy effect of candidate actions, drops actions it has low confidence in, and checks the rest against operator-defined safety constraints. It sends the chosen actions to the local control system, which verifies them against its own constraints. If they pass, the local control system implements them on the cooling plant; what happens to an instruction that fails is inferred. If an operator exits AI control mode, the local control system runs the plant on its on-site rules and heuristics.ALTwithin local constraintselse: outside local constraintsOPToperator exits AI mode1. cooling system snapshot · Documented in source [2]1Plant sensorsCloud AIcooling system snapshot2. predict energy of candidate actions · Documented in source [2]2Cloud AIpredict energy of candidate actions3. drop low-confidence actions · Documented in source [2]3Cloud AIdrop low-confidence actions4. check operator safety constraints · Documented in source [2]4Cloud AIcheck operator safety constraints5. chosen actions · Documented in source [2]5Cloud AILocal control systemchosen actions6. implement actions · Documented in source [2]6Local control systemCooling plantimplement actions7. hold current settings · Inferred, not documented in the sources7Local control systemhold current settings8. exit AI control mode · Documented in source [2]8Data center operatorsLocal control systemexit AI control mode9. on-site rules and heuristics · Documented in source [2]9Local control systemCooling planton-site rules and heuristicsOne five-minute cycle of AI cooling controlThe plant sensors send a snapshot of the cooling system to the cloud AI. The cloud AI predicts the energy effect of candidate actions, drops actions it has low confidence in, and checks the rest against operator-defined safety constraints. It sends the chosen actions to the local control system, which verifies them against its own constraints. If they pass, the local control system implements them on the cooling plant; what happens to an instruction that fails is inferred. If an operator exits AI control mode, the local control system runs the plant on its on-site rules and heuristics.ALTwithin local constraintselse: outside local constraintsOPToperator exits AI mode1. cooling system snapshot · Documented in source [2]1cooling systemsnapshot2. predict energy of candidate actions · Documented in source [2]2predict energyof candidateactions3. drop low-confidence actions · Documented in source [2]3droplow-confidenceactions4. check operator safety constraints · Documented in source [2]4check operatorsafetyconstraints5. chosen actions · Documented in source [2]5chosen actions6. implement actions · Documented in source [2]6implementactions7. hold current settings · Inferred, not documented in the sources7hold currentsettings8. exit AI control mode · Documented in source [2]8exit AI control mode9. on-site rules and heuristics · Documented in source [2]9on-site rulesand heuristicsPlant sensors · Device · Documented in source [2]PlantsensorsCloud AI · AI model · Documented in source [2]Cloud AILocal control system · System · Documented in source [2]Local controlsystemCooling plant · Device · Documented in source [1]Cooling plantData center operators · Team · Documented in source [2]Data centeroperatorsOne five-minute cycle of AI cooling controlThe plant sensors send a snapshot of the cooling system to the cloud AI. The cloud AI predicts the energy effect of candidate actions, drops actions it has low confidence in, and checks the rest against operator-defined safety constraints. It sends the chosen actions to the local control system, which verifies them against its own constraints. If they pass, the local control system implements them on the cooling plant; what happens to an instruction that fails is inferred. If an operator exits AI control mode, the local control system runs the plant on its on-site rules and heuristics.ALTwithin local constraintselse: outside local constraintsOPToperator exits AI mode1. cooling system snapshot · Documented in source [2]1cooling systemsnapshot2. predict energy of candidate actions · Documented in source [2]2predict energy ofcandidate actions3. drop low-confidence actions · Documented in source [2]3droplow-confidenceactions4. check operator safety constraints · Documented in source [2]4check operatorsafety constraints5. chosen actions · Documented in source [2]5chosen actions6. implement actions · Documented in source [2]6implement actions7. hold current settings · Inferred, not documented in the sources7hold currentsettings8. exit AI control mode · Documented in source [2]8exit AI control mode9. on-site rules and heuristics · Documented in source [2]9on-site rulesand heuristicsPlant sensors · Device · Documented in source [2]Plant sensorsCloud AI · AI model · Documented in source [2]Cloud AILocal control system · System · Documented in source [2]Local controlsystemCooling plant · Device · Documented in source [1]Cooling plantData center operators · Team · Documented in source [2]Data centeroperatorsOne five-minute cycle of AI cooling controlThe plant sensors send a snapshot of the cooling system to the cloud AI. The cloud AI predicts the energy effect of candidate actions, drops actions it has low confidence in, and checks the rest against operator-defined safety constraints. It sends the chosen actions to the local control system, which verifies them against its own constraints. If they pass, the local control system implements them on the cooling plant; what happens to an instruction that fails is inferred. If an operator exits AI control mode, the local control system runs the plant on its on-site rules and heuristics.ALTwithin local constraintselse: outside local constraintsOPToperator exits AI mode1. cooling system snapshot · Documented in source [2]1cooling system snapshot2. predict energy of candidate actions · Documented in source [2]2predict energy ofcandidate actions3. drop low-confidence actions · Documented in source [2]3drop low-confidenceactions4. check operator safety constraints · Documented in source [2]4check operatorsafety constraints5. chosen actions · Documented in source [2]5chosen actions6. implement actions · Documented in source [2]6implement actions7. hold current settings · Inferred, not documented in the sources7hold current settings8. exit AI control mode · Documented in source [2]8exit AI control mode9. on-site rules and heuristics · Documented in source [2]9on-site rules and heuristicsPlant sensors · Device · Documented in source [2]Plant sensorsCloud AI · AI model · Documented in source [2]Cloud AILocal control system · System · Documented in source [2]Local controlsystemCooling plant · Device · Documented in source [1]Cooling plantData center operators · Team · Documented in source [2]Data centeroperators
    • AI component
    • Data
    • Trigger or control
    • Inferred, not documented
    Sources [1][2]
    Every action passes two constraint checks, and operators can return the plant to its standard rules at any time.

    An instruction that fails the local check most likely leaves the current settings in place, the conservative default for a plant like this.

    In Kava’s words, the system makes more fine-tuned adjustments than a person normally would10. Two cases show them:

    • Tornado watch: At a Midwest data center, the AI changed the plant’s settings in a way that the operators found counterintuitive. On closer inspection, the change was what saved energy in those conditions10.
    • Winter conditions: The AI learned to produce colder than normal water, which cuts the energy needed for cooling. “Rules don’t get better over time, but AI does,” said Dan Fuenffinger, one of Google’s data center operators2.

    Results

    The following table lists the published results.

    Metric Before After Scope and timeframe Reported by
    Cooling efficiency in kW/ton Historical baseline before AI control 12% better Initial launch of direct AI control Google DeepMind, measured2
    Cooling efficiency in kW/ton Historical baseline before AI control around 30% better Nine months after launch, reported August 2018 Google DeepMind, measured2
    Energy used for cooling Not disclosed 40% lower One live data center, recommendation system test, reported July 2016 Google DeepMind, pilot1
    PUE overhead Not disclosed 15% lower Same test, after electrical losses and other non-cooling overhead Google DeepMind, pilot1
    PUE of a lightly loaded new data center Between 1.3 and 1.2 1.1 or 1.09 Newly launched sites with AI-controlled cooling, August 2018 Joe Kava, Google, via Data Center Knowledge, estimated10
    PUE prediction error Not applicable Mean absolute error of 0.004 Test data set from Google data centers, 2014 paper Google, measured4

    The metrics measure the following:

    • Cooling efficiency in kW/ton: Measures the energy put in per ton of cooling delivered, against the historical baseline before AI control. DeepMind puts the rise over nine months down to the system getting better with more data2.
    • Annual savings: In August 2018, Kava put the fully automated version’s savings at about 30 percent annually, with further improvements expected10.
    • Energy used for cooling and PUE overhead: Come from the 2016 test of the recommendation system, where a typical test day had periods with the recommendations on and off. The test also produced the lowest PUE the site had ever seen1.
    • PUE of a new data center: A newly launched site runs least efficiently while it’s lightly loaded, because the network fabric across the whole data center needs power. The system does especially well at these sites10.
    • PUE prediction error: Measures how closely Gao’s 2014 model predicted PUE on test data from Google data centers4.
    • Energy cost: Kava projected that the project could generate millions of dollars in energy savings3.

    Lessons learned

    The AI ran production cooling plants, not a test rig. It controlled multiple production data centers for months, and its gain was tracked against a historical baseline over nine months2. The push for autonomy came from the operators, and the AI found moves that people hadn’t made, from spreading load across more equipment to using winter conditions and a tornado watch2, 10.

    The safety design cost energy savings. Confining the system to a narrower operating regime meant accepting smaller energy reductions in exchange for safety and reliability2. Kava said that AI still does poorly in situations “outside of the envelope of its training,” which is why people stay on site for the corner cases10.

    The models depend on their training data and their setting. The error of Gao’s 2014 model rose for PUE values above 1.14, where training data was scarce, so the analyst and the operator still had to use judgment4. When DeepMind, Google and Trane took a similar algorithm into commercial buildings, they ran into problems with evaluation, learning from offline data, and constraint satisfaction5.

    An outside expert questioned the size of the prize. Jonathan Koomey, an expert on data center energy, called the use of machine learning “an important development” but pointed out that cooling is around 10% of a data center’s energy use. “The possibilities on the compute side are tenfold bigger than for cooling,” he told MIT Technology Review3.

    The headline figures differ in their details. DeepMind’s around 30% is an average gain in kW/ton after nine months, while Kava’s about 30 percent annually names no metric or baseline2, 10. DeepMind’s 2016 post says both that cooling energy fell “by up to 40 percent” and that the system “consistently” achieved 40%1.

    Every figure is Google’s or DeepMind’s own, from their blog posts, Gao’s paper, and Kava’s interviews, which MIT Technology Review and Data Center Knowledge reported1, 2, 3, 4, 10. The dated results are from 2016 and 2018. Google’s fleet-wide average PUE was 1.09 in 2025, and Google reports it as a fleet figure without linking it to AI cooling9.

    Case study scorecard

    Build this solution yourself

    Analysis

    What you need

    To build this solution, you need the following in place:

    • A long, dense sensor history: Gao’s first model learned the plant’s nonlinear behavior from about two years of five-minute readings of the plant, the weather, and the IT load4.
    • A site control system that checks outside instructions: Google’s local control system verifies each instruction against its own limits and falls back to its own rules, so the AI isn’t the last line of defense2.
    • A model for each site: Google trains a model for each site’s specific cooling architecture rather than one for the fleet, because each data center’s design differs from the others10.

    Reference architecture

    Process optimization and control

    A process optimization and control solution learns from a site's operating data how a physical process responds to its settings and works out better settings as conditions change. A process model predicts how the process responds to live readings, and an optimizer picks the settings that do best within limits that operators set. An operator accepts and enters each recommendation, or the control system carries the settings out while operators watch and can take the process back.

    A check mark shows a building block that this case study's sources document.

    Open the reference architecture

    Others who built it

    • Meta has used simulator-based reinforcement learning to set the supply airflow in a pilot data center region since 2021. It cut supply fan energy by 20% and water use by 4% on average, and it’s rolling the approach out to its existing data centers7.
    • Equinix used etalytics’ etaMIND AI Suite to coordinate the cooling setpoints of its FR6 data center in Frankfurt, saving 900 MWh a year8.
    • Trane Technologies worked with DeepMind and Google on reinforcement learning control of the chiller plants in two commercial buildings, with energy savings of about 9% and 13% against Trane’s heuristics-based controllers5.

    Cite this case study

    Enterprise AI Case Studies. "AI control cuts cooling energy in Google's data centers." Updated Nov 19, 2026. https://case-studies.ai/case-studies/operational-technology/OT-008-data-center-cooling-optimization/

    @misc{csai-ot-008,
      author = {{Enterprise AI Case Studies}},
      title = {{AI control cuts cooling energy in Google's data centers}},
      year = {2026},
      note = {Updated 2026-11-19},
      url = {https://case-studies.ai/case-studies/operational-technology/OT-008-data-center-cooling-optimization/}
    }

    Sources

    The following reporting, and every passage quoted from it, belongs to its publisher, not to this site. Sources and ownership

    1. Source 1:

      DeepMind AI Reduces Google Data Centre Cooling Bill by 40%

      OrganizationGoogle DeepMind, Jul 20, 201620 Jul 2016Accessed Nov 16, 202616 Nov 2026

      Supporting excerpts (15)
      • we've managed to reduce the amount of energy we use for cooling by up to 40 percent
      • our data centres - which contain servers powering Google Search, Gmail, YouTube, etc. - also generate a lot of heat that must be removed to keep the servers running. This cooling is typically accomplished via large industrial equipment such as pumps, chillers and cooling towers.
      • The equipment, how we operate that equipment, and the environment interact with each other in complex, nonlinear ways. Traditional formula-based engineering and human intuition often do not capture these interactions.
      • The system cannot adapt quickly to internal or external changes (like the weather). This is because we cannot come up with rules and heuristics for every operating scenario.
      • Each data centre has a unique architecture and environment. A custom-tuned model for one system may not be applicable to another.
      • Given how sophisticated Google's data centres are already
      • we began applying machine learning two years ago to operate our data centres more efficiently
      • over the past few months, DeepMind researchers began working with Google's data centre team
      • taking the historical data that had already been collected by thousands of sensors within the data centre - data such as temperatures, power, pump speeds, setpoints, etc. - and using it to train an ensemble of deep neural networks
      • we trained the neural networks on the average future PUE (Power Usage Effectiveness), which is defined as the ratio of the total building energy usage to the IT energy usage
      • Since our objective was to improve data centre energy efficiency
      • We then trained two additional ensembles of deep neural networks to predict the future temperature and pressure of the data centre over the next hour. The purpose of these predictions is to simulate the recommended actions from the PUE model, to ensure that we do not go beyond any operating constraints.
      • We tested our model by deploying on a live data centre. The graph below shows a typical day of testing, including when we turned the machine learning recommendations on, and when we turned them off.
      • Our machine learning system was able to consistently achieve a 40 percent reduction in the amount of energy used for cooling, which equates to a 15 percent reduction in overall PUE overhead after accounting for electrical losses and other non-cooling inefficiencies. It also produced the lowest PUE the site had ever seen.
      • We are planning to roll out this system more broadly
    2. Source 2:

      Safety-first AI for autonomous data centre cooling and industrial control

      OrganizationGoogle DeepMind, Aug 17, 201817 Aug 2018Accessed Nov 16, 202616 Nov 2026

      Supporting excerpts (28)
      • In 2016, we jointly developed an AI-powered recommendation system to improve the energy efficiency of Google's already highly-optimised data centres.
      • instead of human-implemented recommendations, our AI system is directly controlling data centre cooling, while remaining under the expert supervision of our data centre operators. This first-of-its-kind cloud-based control system is now safely delivering energy savings in multiple Google data centres.
      • Every five minutes, our cloud-based AI pulls a snapshot of the data centre cooling system from thousands of sensors and feeds it into our deep neural networks, which predict how different combinations of potential actions will affect future energy consumption.
      • The AI system then identifies which actions will minimise the energy consumption while satisfying a robust set of safety constraints. Those actions are sent back to the data centre, where the actions are verified by the local control system and then implemented.
      • The idea evolved out of feedback from our data centre operators who had been using our AI recommendation system.
      • although the system had taught them some new best practices
      • spreading the cooling load across more, rather than less, equipment
      • implementing the recommendations required too much operator effort and supervision
      • they wanted to know whether we could achieve similar energy savings without manual implementation
      • use eight different mechanisms to ensure the system will behave as intended at all times
      • One simple method we've implemented is to estimate uncertainty.
      • Another method is two-layer verification.
      • Most importantly, our data centre operators are always in control
      • Find out about the other safety mechanisms we've developed, below
      • and there are billions
      • our AI agent calculates its confidence that this is a good action. Actions with low confidence are eliminated from consideration.
      • Optimal actions computed by the AI are vetted against an internal list of safety constraints defined by our data centre operators. Once the instructions are sent from the cloud to the physical data centre, the local control system verifies the instructions against its own set of constraints.
      • This redundant check ensures that the system remains within local constraints and operators retain full control of the operating boundaries.
      • our data centre operators are always in control and can choose to exit AI control mode at any time
      • the on-site rules and heuristics that define the automation industry today
      • Whereas our original recommendation system had operators vetting and implementing actions, our new AI control system directly implements the actions.
      • We've purposefully constrained the system's optimisation boundaries to a narrower operating regime to prioritise safety and reliability, meaning there is a risk/reward trade off in terms of energy reductions.
      • Despite being in place for only a matter of months
      • the system is already delivering consistent energy savings of around 30 percent on average, with further expected improvements. That's because these systems get better over time with more data
      • Our optimisation boundaries will also be expanded as the technology matures
      • This graph plots AI performance over time relative to the historical baseline before AI control. Performance is measured by a common industry metric for cooling energy efficiency, kW/ton (or energy input per ton of cooling achieved). Over nine months, our AI control system performance increases from a 12 percent improvement (the initial launch of autonomous control) to around a 30 percent improvement.
      • Dan Fuenffinger, one of Google's data centre operators who has worked extensively alongside the system
      • It was amazing to see the AI learn to take advantage of winter conditions and produce colder than normal water, which reduces the energy required for cooling within the data centre. Rules don't get better over time, but AI does.
    3. Source 3:

      Google just gave control over data center cooling to an AI

      IndependentMIT Technology Review, Aug 17, 201817 Aug 2018By Will KnightAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (13)
      • Google revealed today that it has given control of cooling several of its leviathan data centers to an AI algorithm.
      • This system previously made recommendations to data center managers, who would decide whether or not to implement them, leading to energy savings of around 40 percent in those cooling systems.
      • It's the first time that an autonomous industrial control system will be deployed at this scale, to the best of our knowledge
      • says Mustafa Suleyman, head of applied AI at DeepMind
      • The algorithm exploits a technique known as reinforcement learning, which learns through trial and error.
      • DeepMind fed its new algorithm information gathered from Google data centers and let it determine what cooling configurations would reduce energy consumption.
      • The project could generate millions of dollars in energy savings and may help the company lower its carbon emissions, says Joe Kava, vice president of data centers for Google.
      • Kava says managers trusted the earlier system and had few concerns about delegating greater control to an AI.
      • A data center manager can watch the system in action, see what the algorithm's confidence level is about the changes it wants to make, and intervene if it seems to be doing something untoward.
      • Jonathan Koomey, one of the world's leading experts on data center energy usage
      • Use of machine learning is an important development
      • cooling accounts for a relatively small amount of a center's energy use, around 10 percent
      • The possibilities on the compute side are tenfold bigger than for cooling.
    4. Source 4:

      Machine Learning Applications for Data Center Optimization

      OrganizationGoogle, 2014By Jim GaoDocumentAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (30)
      • Google's historical PUE performance from an annualized fleet-wide PUE of 1.21 in 2008 to 1.12 in 2013
      • the overall pace of PUE reduction has slowed given diminishing returns and the limitations of existing cooling technology
      • best practice techniques such as hot air containment, water side economization, and extensive monitoring are now commonplace in large-scale DCs
      • A typical large-scale DC generates millions of data points across thousands of sensors every day, yet this data is rarely used for applications other than monitoring purposes.
      • a simple change to the cold aisle temperature setpoint will produce load variations in the cooling infrastructure (chillers, cooling towers, heat exchangers, pumps, etc.), which in turn cause nonlinear changes in equipment efficiency
      • Using standard formulas for predictive modeling often produces large errors because they fail to capture such complex interdependencies.
      • Testing each and every feature combination to maximize efficiency would be unfeasible given time constraints, frequent fluctuations in the IT load and weather conditions, as well as the need to maintain a stable DC environment.
      • Currently, it's very difficult for an operator to predict the effect of a plant configuration change on PUE prior to enacting the changes.
      • a neural network is selected as the mathematical framework for training DC energy efficiency models
      • neural networks do not require the user to predefine the feature interactions in the model
      • including the IT load, weather conditions, number of chillers and cooling towers running, equipment setpoints, etc.
      • The neural network utilizes 5 hidden layers, 50 nodes per hidden layer and 0.001 as the regularization parameter.
      • The training dataset contains 19 normalized input variables and one normalized output variable (the DC PUE), each spanning 184,435 time samples at 5 minute resolution (approximately 2 years of operational data).
      • 70% of the dataset is used for training with the remaining 30% used for cross-validation and testing.
      • predict PUE within a range of 0.004 +/- 0.005 (mean absolute error +/- 1 standard deviation)
      • The model has been extensively tested and validated at Google DCs.
      • Alejandro Lameda Lopez and Winnie Lam have been instrumental in model deployment on live Google data centers.
      • suggested a theoretical 0.005 reduction in PUE by increasing the cooling tower LWT and chilled water injection pump setpoints by 3F
      • This simulated PUE reduction was subsequently verified with experimental test results
      • Catching Erroneous Meter Readings
      • The local DC operations teams detected the anomalies
      • This required installing automated natural gas meters at each of Google's DCs.
      • local variations in the type of gas meter used caused confusion regarding erroneous measurement units
      • actual PUE values exceeded the predicted PUE values
      • Through a combination of PUE simulations and local expertise, the team selected a new set of operational parameters that reduced the PUE by ~0.02 compared to the previous configuration.
      • a planned upgrade to the electrical infrastructure required rerouting ~40% of the server traffic
      • Splitting the same cooling load across more towers requires a lower mean fan speed per tower.
      • the model error generally increases for PUE values greater than 1.14 due to the scarcity of training data corresponding to those values
      • Machine learning applications are limited by the quality and quantity of the data inputs.
      • It is up to the analyst and DC operator to apply reasonable discretion when evaluating model predictions.
    5. Source 5:

      Controlling Commercial Cooling Systems Using Reinforcement Learning

      AcademicarXiv, Dec 14, 202214 Dec 2022DocumentAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (10)
      • Building on expertise that began with cooling Google's data centers more efficiently, we recently conducted live experiments on two real-world facilities in partnership with Trane Technologies, a building management system provider.
      • The core RL algorithm that we focus on in this paper is similar to the one used for controlling the cooling in Google's data centers (Gamble and Gao, 2018).
      • Learns an ensemble of neural networks for predicting the action value function and observation constraint violations.
      • The action value function has one output corresponding to energy consumption and a separate output for each of the the observation constraints.
      • Discards, at each time step, the actions that are known to violate the action constraints or predicted to violate the observation constraints.
      • Selects one of the remaining actions based on an exploration-exploitation tradeoff involving the ensemble standard deviation.
      • cooling demand can change quite frequently in a commercial building depending on occupancy level, whereas in a Google data center it tends to be relatively stable
      • These live experiments had a variety of challenges in areas such as evaluation, learning from offline data, and constraint satisfaction.
      • resulting in energy savings of approximately 9% and 13% respectively at the two live experiment sites
      • heuristics-based controllers provided by Trane
    6. Source 6:

      Data Center Cooling using Model-predictive Control

      AcademicGoogle, 2018Accessed Nov 16, 202616 Nov 2026

      Supporting excerpts (3)
      • Proceedings of the Thirty-second Conference on Neural Information Processing Systems (NeurIPS-18), Montreal, QC (2018)
      • the task of regulating temperatures and airflow inside a large-scale data center (DC)
      • Adopting a data-driven model-based approach, we demonstrate that an RL agent is able to effectively and safely regulate conditions inside a server floor in just a few hours, while improving operational efficiency relative to existing controllers.
    7. Source 7:

      Simulator-based reinforcement learning for data center cooling optimization

      OrganizationMeta, Sep 10, 202410 Sep 2024Accessed Nov 16, 202616 Nov 2026

      Supporting excerpts (3)
      • Using simulator-based reinforcement learning, we have, on average, reduced the supply fan energy consumption at one of the pilot regions by 20% and water usage by 4% across various weather conditions.
      • In 2021, we started a pilot at one of Meta's data center regions - having the RL model directly controlling the supply airflow setpoint.
      • We're also currently rolling out our RL approach to data center cooling to our existing data centers.
    8. Source 8:

      Optimal Control for Data Center Cooling Systems

      Partner or vendoretalyticsAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (3)
      • the addressed Data Center "FR6" in Frankfurt am Main
      • the implementation of the etaMIND AI Suite
      • By coordinating and refining the cooling system equipment's setpoints, we saved 900 MWh/year in electrical energy
    9. Source 9:

      Growing the internet while reducing energy consumption

      OrganizationGoogleAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (1)
      • In 2025, the average annual power usage effectiveness for our global fleet of data centers was 1.09.
    10. Source 10:

      Google is Switching to a Self-Driving Data Center Management System

      IndependentData Center Knowledge, Aug 2, 20182 Aug 2018By Yevgeniy SverdlikAccessed Nov 16, 202616 Nov 2026

      Supporting excerpts (30)
      • described in 2014, when he first revealed that the company was using AI to improve data center energy efficiency
      • That system, developed by Google's then data center engineer Jim Gao, was implemented as a recommendation engine.
      • We had a standalone model that we would run, and it would spit out recommendations, and then the engineers and the operators in the facility would go and change the setpoints on the chillers, and the heat exchangers, and the pumps, and all that to match what the AI system said
      • Kava said in a recent interview with Data Center Knowledge
      • The company is now aggressively rolling out what Kava referred to as a
      • Instead of simply making recommendations, this tier-two system makes all the cooling-plant tweaks on its own, continuously, in real-time.
      • could shave up to 40 percent off a facility cooling system's total energy use
      • The new fully automated version is saving about 30 percent annually, and the company expects further improvements.
      • Gao has since joined the DeepMind team, according to Kava.
      • It's looking at the same input variables: outside air temperature, barometric pressure, wet-bulb temperature, dry-bulb temperature, dew point, power load in the data center, air pressure in the back of the servers where hot air comes out, and so on
      • and so on – 21 variables total
      • It crunches all that data, and, based on the weather conditions and the load in the data center, it optimizes PUE
      • Under a recent tornado watch, the AI system managing the cooling plant at one of Google's data centers in the Midwest changed the plant's settings in a way which the facility's human operators found counterintuitive.
      • After closer scrutiny, however, it did what had to be done to save energy under those specific circumstances.
      • It's making more fine-tuned adjustments than you would normally make as a human
      • The system does especially well when the company launches new data centers
      • Typically, a newly launched data center runs at its least efficient, because it's not utilizing most of the underlying infrastructure's capacity.
      • the network fabric that stretches across the entire data center needs electricity
      • Lightly loaded, a newly launched Google data center's typical PUE is between 1.3 and 1.2, he said. With the cooling system controlled by AI, it can go down to 1.1 or 1.09.
      • And you start to put in the guardrails to make sure that bad things can't happen, and then you start to launch fully automated systems instead of semiautomated systems
      • And if the fully automated systems actually start running better, then you start deploying more of those.
      • The more runtime you accumulate and the more data you collect, the better your machine-learning algorithm gets, and the more comfortable you get with the idea of giving it more control.
      • If you were to tell a machine to optimize for PUE, the machine might tell you to shut down all of the servers
      • each of its data centers is different enough from the others that the AI-based automated control system cannot be rolled out across them all at once
      • at least some changes to the designs are made once about every 18 months
      • You have to train your model for that specific architecture
      • We still have people there, because they still have to do all the maintenance
      • Instead of trying to tune the system themselves, they can focus more of their time on preventative maintenance and corrective repairs.
      • AI still does poorly in situations
      • outside of the envelope of its training